Refrigerated air dryer
Refrigeration dryers employ two heat exchangers, one for air-to-air and one for air-to-refrigeration. However, there is also a single Trisab heat exchanger that combines both functions. The compressors used in this type of dryer are usually of the hermetic type and the most common gas used is R-134a. The goal of having two heat exchangers is that the cold outgoing air cools down the hot incoming air and reduces the size of compressor required. At the same time the increase in the temperature of outgoing air prevents re-condensation.
Commonly a coalesing prefilter is installed immediately upstream of a refrigerated dryer to remove lubricating oil and other contaminants that have the potential to foul the dryer's heat exchangers.
Specifications
MODEL | Flow rate | End Conn. | Dimensions in mm | Weight | |||
---|---|---|---|---|---|---|---|
M3/Hr | SCFM | In / Out | Height | Width | Depth | Kg | |
BRD-20 | 20 | 12 | 1/2" | 460 | 590 | 550 | 38 |
BRD-32 | 32 | 19 | 1/2" | 460 | 590 | 550 | 40 |
BRD-51 | 51 | 30 | 3/4" | 460 | 590 | 550 | 43 |
BRD-54 | 54 | 32 | 3/4" | 460 | 590 | 550 | 38 |
BRD-105 | 105 | 62 | 3/4" | 460 | 590 | 550 | 40 |
BRD-135 | 135 | 79 | 1" | 460 | 590 | 550 | 43 |
BRD-180 | 180 | 106 | 1" | 595 | 690 | 680 | 61 |
BRD-250 | 250 | 147 | 1" | 595 | 860 | 860 | 81 |
BRD-300 | 300 | 177 | 1 1/4" | 595 | 860 | 860 | 96 |
BRD-360 | 360 | 212 | 1 1/2" | 595 | 860 | 860 | 109 |
BRD-450 | 450 | 265 | 2" | 595 | 860 | 860 | 114 |
BRD-588 | 588 | 346 | 2" | 630 | 1200 | 960 | 216 |
BRD-708 | 708 | 417 | 2" | 630 | 1200 | 960 | 225 |
BRD-828 | 828 | 487 | 2 1/2" | 870 | 1710 | 1200 | 248 |
BRD-1008 | 1008 | 593 | 2 1/2" | 870 | 1710 | 1200 | 298 |
BRD-1260 | 1260 | 742 | 2 1/2" | 870 | 1710 | 1200 | 327 |
BRD-1560 | 1560 | 918 | NB 80 | 870 | 1710 | 1200 | 375 |
BRD-1890 | 1890 | 1112 | NB 80 | 870 | 1710 | 1200 | 460 |
BRD-2520 | 2520 | 1483 | NB 100 | 1050 | 1810 | 1450 | 525 |
BRD-3090 | 3090 | 1819 | NB 100 | 1050 | 1810 | 1450 | 585 |
BRD-3630 | 3530 | 2137 | NB 100 | 1450 | 2050 | 1650 | 690 |
Operating Conditions | |||||||
Normal | Maximum | ||||||
Working Pressure | 7 to 12.5 Bar | 16 Bar | |||||
Inlet Temperature | 25°C | 55°C | |||||
Dew Point | -3°C | -10 °C | |||||
Above flow rates are at 7 Bar,35 ℃,Standard Power supply ; Model BRD20 to 708 220V/1Ph,50Hz and BRD828 to 3660 440V/3Ph,50Hz. | |||||||
Usage/Application: | ◼ Instrument and Control Air ◼Process Control Instruments ◼ Textile Machines◼Machine tools ◼ Bearing air ◼ Air Motors and Heavy Air motor ◼ miniature◼Packaging machine ◼ Pneumatic cylinder ◼ Sensors in fluid technology ◼ Sand blasting unit ◼ Handling of food and beverages ◼ Semi conductor manufacturing ◼ Wind tunnels◼Pharmaceutical manufacturing ◼ Conveyance of hygroscopic products ◼ Paint spray and Powder coating |